Issue 13 February 2001 Troubleshooting 8 - 9
BTJ1 Battery Thermal Major
A Battery Thermal Protection (BTP) module
wired to the BTP inputs of Galaxy TB3 is
reporting a battery temperature above its major
alarm threshold (varies with BTP type).
BTN1 Battery Thermal Minor
A Battery Thermal Protection (BTP) module
wired to the BTP inputs of Galaxy TB3 is
reporting a battery temperature above its minor
alarm threshold (varies with BTP type).
CCH1 Configuration Changed
A change has been made to a configuration
setting. This is a latched event, remaining active
until cleared by a user.
CDFA1 Converter Distribution Fuse
A converter distribution module connected to the
controller’s serial bus is reporting an operated fuse
in it’s output distribution.
CDID1 Converter ID Conflict
The ID for a converter connected to the
controller’s serial bus is the same as that of a
previously installed converter.
CEA1 Connected Equip Alarm 1
Equipment monitored by Galaxy through Data
Switch Port-1 is reporting an alarm.
CEA2 Connected Equip Alarm 2
Equipment monitored by Galaxy through Data
Switch Port-2 is reporting an alarm.
CEA3 Connected Equip Alarm 3
Equipment monitored by Galaxy through Data
Switch Port-3 is reporting an alarm.
CEA4 Connected Equip Alarm 4
Equipment monitored by Galaxy through Data
Switch Port-4 is reporting an alarm.
CEA5 Connected Equip Alarm 5
Equipment monitored through Data Switch Port-5
is reporting an alarm. (Millennium only.)
CEA6 Connected Equip Alarm 6
Equipment monitored through Data Switch Port-6
is reporting an alarm. (Millennium only.)
CFA1 Converter Fail
A converter connected to Galaxy’s serial bus has
failed.
CFJ1 Converter Fan Major
Two or more converters connected to the
controller’s serial bus are reporting fan failures.
CFN1 Converter Fan Minor
A converter connected to the controller’s serial
bus is reporting a fan failure.
Table 8-A: Galaxy Alarms