BTJ1 Battery Thermal Major
A Battery Thermal Protection (BTP) module
wired to the BTP inputs of Galaxy TB3 is
reporting a battery temperature above its major
alarm threshold (varies with BTP type).
BTN1 Battery Thermal Minor
A Battery Thermal Protection (BTP) module
wired to the BTP inputs of Galaxy TB3 is
reporting a battery temperature above its minor
alarm threshold (varies with BTP type).
CCH1 Configuration Changed
A change has been made to a configuration
setting. This is a latched event, remaining active
until cleared by a user.
CDFA1 Converter Distribution Fuse
A converter distribution module connected to the
controller’s serial bus is reporting an operated fuse
in it’s output distribution.
CDID1 Converter ID Conflict
The ID for a converter connected to the
controller’s serial bus is the same as that of a
previously installed converter.
CEA1 Connected Equip Alarm 1
Equipment monitored by Galaxy through Data
Switch Port-1 is reporting an alarm.
CEA2 Connected Equip Alarm 2
Equipment monitored by Galaxy through Data
Switch Port-2 is reporting an alarm.
CEA3 Connected Equip Alarm 3
Equipment monitored by Galaxy through Data
Switch Port-3 is reporting an alarm.
CEA4 Connected Equip Alarm 4
Equipment monitored by Galaxy through Data
Switch Port-4 is reporting an alarm.
CEA5 Connected Equip Alarm 5
Equipment monitored through Data Switch Port-5
is reporting an alarm. (Millennium only.)
CEA6 Connected Equip Alarm 6
Equipment monitored through Data Switch Port-6
is reporting an alarm. (Millennium only.)
CFA1 Converter Fail
A converter connected to Galaxy’s serial bus has
failed.
CFJ1 Converter Fan Major
Two or more converters connected to the
controller’s serial bus are reporting fan failures.
CFN1 Converter Fan Minor
A converter connected to the controller’s serial
bus is reporting a fan failure.
Table 8-A: Galaxy Alarms
Symbol Designation Explanation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals