Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 8 T1.317 Objects and Attributes Issue 13 February 2001
Table B-6: Boost Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Boost BST
Identifier IDE TEXT BS1
Description DES TEXT X X X Boost Control 1
State STT TEXT QRCT, MANUAL, BTP, TIMED
AUTO, OFF
Boost Enable BSE NUMBER X X X 0:disable 1:enable (HW,SW)
External Timer Boost Enable TBE NUMBER X X X 0:disable 1:enable (HW,SW)
Battery Therm. Protect Enable BTP NUMBER X X X 0:disable 1:enable
Auto Mode ATM TEXT X X X OFF,QRCT,TIMED
Timed Manual Duration TMD NUMBER X X X 1-80:8 hours
Auto Multiplication Factor AMF NUMBER X X X 1-9:5
Current Term Voltage Thresh CTV NUMBER X X X 20-30:26 or 52:40-60:52 volts
Current Term Current Thresh CTA NUMBER X X X >= 0 amps (default: 50)
Current/Time Ratio CTR NUMBER X X X >= 0 (default: 0)
Alarm Sub-Objects
Boost State Alarm BSA ATTRL