Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 10 T1.317 Objects and Attributes Issue 13 February 2001
Table B-8: Converter Management Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Converter Plant CON
Identifier IDE TEXT CP1
Description DES TEXT X X X Converter Plant 1
DC Voltage VDC NUMBER X X number in volts
DC Current ADC NUMBER X number in amps
Capacity CAP NUMBER number in amps
Voltage Set-Point VSP NUMBER X X X 48-52:50V
Low Voltage Discon Threshold DTH NUMBER X X X 20-25:23V
Low Voltage Recon Threshold RTH NUMBER X X X 22-27:25V
Low Voltage Disconnect Enable LVD NUMBER X X X 0:disable 1:enable
Alarm Sub-Objects
Converter Fail Alarm CFA ATTRL CFA1
Distribution Fuse Alarm DFA ATTRL CDFA1
Converter Fan Minor CFN ATTRL CFN1
Converter Fan Major CFJ ATTRL CFJ1
Id Conflict DID ATTRL CDID1
Multiple Convert Fail Alarm MFA ATTRL CMFA1
DC Converter DCC
Identifier IDE TEXT C01 to C16
Description DES TEXT X X X DC Converter nn
Type TYP TEXT 10 chars
DC Current ADC NUMBER X number in amps
Capacity CAP NUMBER number in amps
State STT TEXT X X ON*, OFF, STANDBY*,
VACANT*
Converter Fail CFA NUMBER 0:inactive 1:active
Distribution Fuse Alarm DFA NUMBER 0:inactive 1:active
ID Conflict DID NUMBER 0:inactive 1:active
* The user may only set the state to ON, STANDBY, or VACANT