Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 24 T1.317 Objects and Attributes Issue 13 February 2001
Table B-18: Miscellaneous Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Call-Back Security CBS
Identifier IDE TEXT CB1
Description DES TEXT X X X Call-Back Security 1
State STT NUMBER X X X 0:off 1:on
Call-Back Phone Number PH1-5 TEXT X X X digit ( ) * # - , space (default: “”)
Connect Baudrate BR1-5 NUMBER X X X 300,1200,2400,4800,9600,14400
Notepad NPD
Identifier IDE TEXT UNP, SNP
Description DES TEXT X X X (Super)User Notepad
Notify State STT NUMBER X X X 0:don’t notify 1:notify
Comment Line CL01-15 TEXT X X X up to 60 chars each (default: “”)
Alarm Cut-off ACO
Identifier IDE TEXT ACO1
Description DES TEXT X X X Alarm Cut-off
State STT NUMBER X X 0:disable 1:enable
Critical ACO State CST NUMBER 0:inactive 1:active
Critical ACO Enable CAE NUMBER X X X 0:disable 1:enable
Critical ACO Timeout CTO NUMBER X X X 1-4 hours
Major ACO State JST NUMBER 0:inactive 1:active
Major ACO Enable JAE NUMBER X X X 0:disable 1:enable
Major ACO Timeout JTO NUMBER X X X 1-4 hours
Minor ACO State NST NUMBER 0:inactive 1:active
Minor ACO Enable NAE NUMBER X X X 0:disable 1:enable
Minor ACO Timeout NTO NUMBER X X X 1-72:8 hours
Alarm Sub-Objects
ACO Active AAC ATTRL AAC1
User Defined Object UDO
Identifier IDE TEXT 6 char (default: Onnn (nnn=1-100)
Description DES TEXT X X X 30 char
Users “build” their user defined objects by following the example below:
Command Comment
ADD UDO,CELL1 - Add a user defined object called CELL1 to the system
ADD CELL1,TEMP - Add the attribute TEMP to CELL1
LIN CELL1 TEMP,C701 - LInk a temperature monitor channel to CELL1 TEMP