Tyco Electronics Galaxy SC Controller J85501F-1
3 - 20 Installation Issue 13 February 2001
For Any of These Rectifiers Used With Any of These Cables Order
Rectifier
Interface
Module
Per
J85501F-1
List
Rectifier
Codes
Amps Volts
Allowed Cable Codes
(Length)
Notes
Commercial H285-226 G62 (job spec)
See Table 3-F for
cable descriptions
L34
J87439A
(SP1 circuit
pack)
200 -48 848532131 (job spec)
Commercial
compatible. See
Table 3-F and
J84739A manual
L34
J85702E1 150 -48 H285-226 G63 (job spec)
Enhanced signal
set with shunt
monitor
L35
L33*
Parallel
Switched
Mode
50 -48
Requires installation of
J85702B2 L5 bay shelf
and cable assembly
Enhanced signal
set with shunt
monitor
L35
All Serial
Rectifiers
All All
847865425 (25 ft;
interconnect for
maximum 200 ft)
Coupler included
with cable
L36
*If existing backplane is J85501F1 L33, use cable H285-266 G56 (no shunt monitoring).
Use backplane module J85501F1 L35 and cable H285-226 G63 for new installations and
shunt monitoring.
Notes:
Modification of control cables for rectifier identification is not required when used with the
Galaxy SC.
Rectifiers connected to Galaxy SC without VI signal disables Energy Management.
Table 3-E: Galaxy Controller Rectifier and Cabling Information