FORM 100.50-NOM7 (808)
25
JOHNSON CONTROLS
3
• The programmable parameter VAV Occupied Heat-
ing must be set to ON to enable the Occupied Heat-
ing With A Space Sensor function.
• The stepped heating control algorithm is:
• Turned ON when the space temperature is less
than the (VAV Setpoint for SAT Reset – 2°F).
• Controls the RAT between the Morning Warm
Up Setpoint and the (Morning Warm Up Setpoint
– 2°F). (See Fig. 8).
• Turned OFF when the space temperature greater
than (VAV Setpoint for SAT reset - 1.5°F).
• Figure 12 illustrates the algorithm for occupied
heating required.
• For hydronic heating:
• The SAT is controlled to the 2
nd
Stage Hydronic
Heat Setpoint.
• The Heat 1 output of the controller is set to con-
trol HIGH during heating.
Unoccupied Heating With A Space Sensor
• The programmable parameter VAV Operation with
Thermostat must be set to OFF and Space Sensor
signal must be reliable.
• For hydronic heating:
• The SAT is controlled to the 2
nd
Stage Hydronic
Heat Setpoint.
• The Heat 1 output of the controller is set to con-
trol HIGH during heating.
Occupied Cooling With A Space Sensor
• The programmable parameter VAV Operation with
Thermostat must be set to OFF and Space Sensor
signal must be reliable.
• The SAT setpoint for cooling is the VAV Cool
Low Temperature Setpoint or VAV Cool High
Temperature Setpoint through comparison of the
space temperature and the VAV Setpoint for SAT
Reset as shown in Figure 12.
Unoccupied Cooling With A Space Sensor
• The programmable parameter VAV Operation with
Thermostat must be set to OFF and Space Sensor
signal must be reliable.
• Cooling is called for according to the algorithm
illustrated in Figure 10.
FIG. 8 – VAV OCCUPIED HEATING TO MAINTAIN
RAT AND MORNING WARM UP
sequentially added
dropped
MWU Setpoint
RET URN AIR TEM PER ATURE (˚F)
-2.0
ON
F
LD06557
• The programmable parameter VAV Occupied Heat-
ing must be set to ON to enable the Occupied Heat-
ing With A Space Sensor function.
• The space temperature is controlled to the Unoc-
cupied Heating Setpoint using the algorithm illus-
trated in Figure 9.
FIG. 9 – VAV UNOCCUPIED STEPPED HEATING
TEMPERATURE CONTROL
LD06558
dropped
SPA CE TEMPERA TURE (˚F)
-0.5˚F
+0.5˚F
UNOCC . HTG. SETPOINT
All heating steps
sequentially added
ON
OFF