JOHNSON CONTROLS
76
FORM 100.50-NOM7 (808)
Service
Table 15 lists the description of the various inputs and outputs, and the respective connections to the MOD-DCU.
TABLE 15 – INPUT/OUTPUT TABLE
I/O NAME
1
INPUT TYPE SIGNAL LEVEL APPLICATION
Space Sensor AI 1 1K RTD ALL
Space Sensor Adjust AI 2 1.5K POT ALL
T’Stat Interface AI 3 0-5V ALL
CO2 AI 4 0-5V DEMAND VENTILATION
Return Temperature AI 8 1K RTD DIFF. ENTH. ECONO
Outside Air Temperature AI 6 1K RTD ALL
Return Air Humidity AI 7 0-10V DIFF. ENTH. ECONO
Outside Air Humidity AI 5 0-10V SINGLE ENTH. ECONO
Duct Static Pressure AI 9 0-5V VAV
Building Static Pressure AI 10 0-5V POWER EXHAUST
Supply Temperature AI 13 IK RTD ALL
* Compressor Circuit #1 Status BI 1 24VAC ALL
** Compressor Circuit #2 Status BI 2 24VAC ALL
Not Used BI 3 24VAC
Furnace Model #1 Status BI 4 24VAC GAS HEAT, 1 MODULE
Furnace Model #2 Status BI 5 24VAC GAS HEAT, 2 MODULE
Furnace Model #3 Status BI 6 24VAC GAS HEAT, 3 MODULE
G (fan) Supply Fan BI 7 24VAC ALL
Occupied/Unoccupied Switch BI 8 24VAC ALL
Shutdown BI 9 24VAC ALL
Smoke Purge BI 10 24VAC ALL
Supply Fan Status (fan proving) BI 11 24VAC ALL
Filter Status (dirty lter) BI 12 24VAC DFS OPTION
HW Freezestat BI 14 24VAC HW
Cool-Heat COR Status BI 15 24VAC ALL
VFD Bypass Input BI 16 24VAC VAV W/ VFD BYPASS
Supply Fan VFD AO 1 0-10V VAV
Exhaust Fan VFD or Damper AO 2 0-10V POWERED EXHAUST
OA / RA Damper & Full AMS AO 3 0-10V ALL
Heating Valve AO 6 0-10V HW
Cooling/Heating Stage #1 BO 1 ALL
Cooling/Heating Stage #2 BO 2 ALL
Cooling/Heating Stage #3 BO 3 ALL
Cooling/Heating Stage #4 BO 4 ALL
Cooling/Heating Stage #5 BO 5 30 TON UNITS
Cooling/Heating Stage #6 BO 6 30 TON UNITS
Cool/Heat Changeover Relay BO 7 ALL
Supply Fan BO 8 ALL
Exhaust Fan BO 9 POWERED EXHAUST
VAV Heat Relay BO 10 VAV
NOTES: AI = Analog Input
BI = Binary Input
AO = Analog Output
BO = Binary Output
* Compressors 1 & 2 combined.
** Compressors 3 & 4 combined.

Table of Contents

Other manuals for York J Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York J Series and is the answer not in the manual?

York J Series Specifications

General IconGeneral
BrandYork
ModelJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals