Note, per this control sequence, both the Master and
Subordinate units must be configured exactly the
same for reliable operation. For example, if one unit is
equipped with an exhaust fan and the other is equipped
with just an On/O exhaust fan, stable operation may
not be possible.
Lost Communications
If communications are lost between the Master unit
and the Subordinate unit, the Subordinate unit will shut
down (if operating) and will not be allowed to operate.
The Master unit can still operate, if necessary.
POWER EXHAUST OPERATION
Power Exhaust Operation is used to control building
pressure. For building pressure control, the unit can
be equipped with the following exhaust air control
congurations:
Two position exhaust fan control based on the out-
side air damper position (1).
Two position exhaust fan control based on the build-
ing pressure (2).
Proportional exhaust fan control based on the build-
ing pressure (3).
Proportional exhaust damper control based on the
building pressure (3).
For Power Exhaust Operation:
The Power Exhaust Enable is programmed and the
supply fan must be running.
Two Position Control Based on OAD Position
Two position control based on OAD position controls
the powered exhaust fan ON or OFF based on the po-
sition of the Outside Air Damper. Two position operation
requires:
Economizer = ON
Constant Volume = ON
Supply Fan = ON
This operation is not available when an OA Flow Sta-
tion is installed.
The Exhaust Fan will be controlled by the OAD position
as follows:
Fan ON when the position = OAD Position for the
Exhaust Fan to Turn On.
Fan OFF when the position = OAD Position for the
Exhaust Fan to Turn OFF.
Fan OFF when Supply Fan = OFF.
and as illustrated in the following gure.
FIG. 14 – OAD POSITION CONTROL
Exhaust Fan
Tu rns Off
OAD Position
for EF to Turn
OFF
ON
OFF
OAD Position
Exhaust F
a
Tu rns On
OAD Position
for EF to Turn
ON
LD06577
Two Position Control Based on Building
Pressure
Two position control based on building pressure controls
the powered exhaust fan on or o based on the pressure
within the building or space.
When the controller is congured for this type of exhaust
system, the controller will monitor the building pres-
sure. When the building pressure reaches or exceeds
the Building Pressure Setpoint plus the Exhaust Control
Oset, the controller will energize the Exhaust Fan BO.
The Exhaust Fan BO will remain energized until the
Building Pressure drops to or below the Building Pres-
sure Setpoint minus the Exhaust Control Oset. The
following gure illustrates this control sequence.
FIG. 15 – BUILDING PRESSURE CONTROL
ON
OFF
Building Pressure
Setpoint
minus Exhaust
Control Offset
plus Exhaust
Control Offset
Exhaust Fan
Tu rns Off
Exhaust Fan
Turns On
LD06578A

Table of Contents

Other manuals for York J Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York J Series and is the answer not in the manual?

York J Series Specifications

General IconGeneral
BrandYork
ModelJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals