Setting #4, Purge
If the smoke purge setting is set to 4 and the Smoke
Purge input is activated, the unit will do the follow-
ing:
Turn ON the Supply Fan full (VFD to 100%).
Energize the VAV Heat Relay and drive all VAV
boxes open.
Turn ON the Exhaust Fan full (VFD/ED to
100%).
Open the Outside Air Damper(s) full.
Close the Return Air Damper full.
Maintain this operation until the Smoke Purge input is
deactivated, then return to normal operation.
Setting #5, Purge w/ Duct Pressure Control
If the smoke purge setting is set to 5 and the Smoke
Purge input is activated, the unit will do the follow-
ing:
Supply Fan
VAV units -Turn ON the Supply Fan VFD and
control to the Duct Static Setpoint.
CV - Turn ON fan (variable output is 100%).
Turn ON the Exhaust Fan full (VFD/ED to
100%).
Open the Outside Air Damper(s) full.
Close the Return Air Damper full.
Maintain this operation until the Smoke Purge input is
deactivated, then return to normal operation.

Table of Contents

Other manuals for York J Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York J Series and is the answer not in the manual?

York J Series Specifications

General IconGeneral
RefrigerantR-410A
Compressor TypeSingle-Stage
Operating Voltage208/230V
Warranty10-year limited warranty on compressor, 5-year limited warranty on parts
Sound LevelAs low as 72 dB
Cooling Capacity1.5 to 5 tons

Related product manuals