DESCRIPTION TEXT ON OCC UNITS
DEFAULT VALUE OCC
VALUE RANGE KEY
57. Cooling Mode Enable ON ON or OFF Unit Setup
58. Heating Mode Enable ON ON or OFF Unit Setup
59. Heat Lockout OAT °F 75°F 0°-100°F Unit Setup
60. Cool Lockout OAT °F 45°F 45°-100°F Unit Setup
61. Cooling SAT Alarm °F 0°F 0°/50°-80°F Unit Setup
62. Heating SAT Alarm °F 0°F 0°/70°-120°F Unit Setup
63. Duct Pressure Limit inwg 3.00 inwg 0.00-5.00 inwg Unit Setup
64. VAV Occupied Heat OFF ON or OFF Unit Setup
65. OA SAT Reset OFF ON or OFF Unit Setup
66. SAT Temper Enable OFF ON or OFF Unit Setup
67. VAV With Thermostat ON ON or OFF Unit Setup
68. VAV Control Oset °F 4.5 2.0 – 6.0 Unit Setup
69. FlexSys Dewpt Reset OFF ON or OFF Unit Setup
70. Exh Dmpr Pos For ON % 80% 0-100% Unit Setup
71. Exh Dmpr Pos For OFF % 20% 0-100% Unit Setup
72. OA Dmpr Pos For ON % 60% 0-100% Unit Setup
73. OA Dmpr Pos For OFF % 20% 0-100% Unit Setup
74. OAH Sensor Enable OFF ON or OFF Unit Setup
75. RAH Sensor Enable OFF ON or OFF Unit Setup
76. Exhaust Cntrl Oset inwg 0.015 inwg 0.010 – 0.050 Unit Setup
77. Economizer Enable ON ON or OFF Unit Setup
78. SAT Econo Loading ON ON or OFF Unit Setup
79. Power Exhaust Enable OFF ON or OFF Unit Setup
80. OA Flow Cntrl Enable OFF ON or OFF Unit Setup
81. Comfort Vent Mode OFF ON or OFF Unit Setup
82. Cmfrt Vent Max Dampr % 75% 0-100% Unit Setup
83. IAQ Sensor Enable OFF ON or OFF Unit Setup
84. IAQ Sensor Span ppm 5000 0 – 10000 Unit Setup
85. MAX DV Multiplier 1.25 1-2 Unit Setup
86. Altitude Ft 1000 0-10000 Ft Unit Setup
87. Morning Warm-Up OFF ON or OFF Unit Setup
88. Max Warm-Up Time min 120 min 0-240 min Unit Setup
89. Pre-Occupancy Purge OFF ON or OFF Unit Setup
90. Purge Schedule 4am - 5am Daily-Holiday Unit Setup
all days hh:mm start-end time
91. Purge OAT High Limit °F 85° 0°-110°F Unit Setup
92. Purge OAT Low Limit °F 55° 0°-110°F Unit Setup
93. Smoke Purge Mode 0 0 – 5 Unit Setup
94. Internal Clk/Sched OFF ON or OFF Unit Setup
95. Weekly Schedule 7am - 6pm 8 start/stop entries Unit Setup
weekdays
96. Holiday Schedule (No Sched) 16 entries Unit Setup
97. Date and Time (none) dd-mm-year Unit Status
hh:mm:ss am/pm
NOTES:
1. Both gas and electric heat are referred to functionally as “stepped”
heating or heating “stages”; both HW (hot water) and steam are
functionally referred to as “hydronic” heat.
NOTES FOR TABLE 7 – SETPOINTS AND VALUES
2. The compressor runtimes and starts and fan runtimes are entered
only when a compressor or fan is replaced.