EasyManua.ls Logo

York YCAS - Table 1 - Motor Protector Dip Switch Setting

York YCAS
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
YORK INTERNATIONAL
FORM 201.19-NM6 (804)
Product Description
* Indicates one lead/phase through motor protector.
Model
No.
Volt.
Code
Chiller
Name- -
Plate RLA
No. Leads
per Phase
Motor Protector
MP OL
Value Set
Dip Switch Settings on MP
128 64 32 16 8 4 2 1
0693
Sys 1 & 2
50 140 2 189 1 0 0 0 0 1 1 0
693
Sys 3
50 124 2 167 1 0 1 0 0 1 1 1
0773
Sys 1 & 2
50 140 2 189 1 0 1 1 1 1 0 1
0773
Sys 3
50 183 *2 124 0 1 1 1 1 1 0 0
0783
Sys 1 & 2
50 124 2 167 1 0 1 0 0 1 1 1
0783
Sys 3
50 168 *2 113 0 1 1 1 0 0 0 1
0873 50 168 *2 113 0 1 1 1 0 0 0 1
0953 50 183 *2 124 0 1 1 1 1 1 0 0
1063
Sys 1 & 2
50 161 2 217 1 1 0 1 1 0 0 1
1063
Sys 3 & 4
50 140 2 189 1 0 1 1 1 1 0 1
1093
Sys 1 & 2
50 183 *2 124 0 1 1 1 1 1 0 0
1093
Sys 3 & 4
50 140 2 189 1 0 1 1 1 1 0 1
1163 50 168 *2 113 0 1 1 1 0 0 0 1
1263 50 183 *2 124 0 1 1 1 1 1 0 0
TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING - (ACROSS THE LINE START - 50 HZ)