96
YORK INTERNATIONAL
FORM 201.19-NM6 (804)
FIG. 52 – MODEL YCAS1063 DIMENSIONS (SI)
Technical Data
DIMENSIONS – YCAS1063 (SI)
All dimensions are in mm
un less oth er wise noted.
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, re li able
operation and ease of maintenance. Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow
pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;
however, the system designer must con sid er potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; con trol panel end to wall - 1.2m;
top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
LD04016
LD04015