YORK INTERNATIONAL
FORM 201.19-NM6 (804)
TABLE 11 – YCAS STYLE G, ACROSS THE LINE START - 50 HZ.
Micro Panel Contents
* Indicates one lead/phase through motor protector.
Model
No.
Volt.
Code
Chiller Name-
Plate RLA
No. Leads per Phase
100% FLA
Of Sys.
MP OL Value Set
0693
Sys 1 & 2
50 140 2 151 189
693
Sys 3
50 124 2 134 167
0773
Sys 1 & 2
50 140 2 151 189
0773
Sys 3
50 183 *2 198 124
0783
Sys 1 & 2
50 124 2 134 167
0783
Sys 3
50 168 *2 181 113
0873 50 168 *2 181 113
0953 50 183 *2 198 124
1063
Sys 1 & 2
50 161 2 174 217
1063
Sys 3 & 4
50 140 2 151 189
1093
Sys 1 & 2
50 183 *2 198 124
1093
Sys 3 & 4
50 140 2 151 189
1163 50 168 *2 181 113
1263 50 183 *2 198 124