42 YORK INTERNATIONAL
FORM 201.18-NM1 (102)
NOTES:
1. For leaving brine temperature below 40°F (4.40°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
TEMPERATURE AND FLOWS
(SI UNITS)
Excessive flow, above the max GPM,
will damage the evaporator.
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0130EC 4.4 12.8 9.3 37.8 -17.7 51.7
0140EC 4.4 12.8 10.7 37.8 -17.7 51.7
0150EC 4.4 12.8 11.5 44.2 -17.7 51.7
0160EC 4.4 12.8 11.9 47.1 -17.7 51.7
0170EC 4.4 12.8 12.8 47.1 -17.7 51.7
0180EC 4.4 12.8 13.8 47.1 -17.7 51.7
0200EC 4.4 12.8 14.4 47.1 -17.7 51.7
0210EC 4.4 12.8 15.6 47.1 -17.7 51.7
0230EC 4.4 12.8 17.2 47.1 -17.7 51.7
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER TEMPERATURE (°F) (GPM
3
) CONDENSER (°F)
YCAS MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0130EC 40 55 147 600 0 125
0140EC 40 55 170 700 0 125
0150EC 40 55 182 747 0 125
0160EC 40 55 188 747 0 125
0170EC 40 55 203 747 0 125
0180EC 40 55 218 747 0 125
0200EC 40 55 228 747 0 125
0210EC 40 55 248 747 0 125
0230EC 40 55 272 747 0 125
Technical Data