51YORK INTERNATIONAL
FORM 201.18-NM1 (102)
ELECTRICAL DATA
7
CHILLER FIELD SUPPLIED WIRING SYSTEM #1 SYSTEM #2
MODEL VOLTS
MCA
1
FACTORY-SUPPLIED BREAKER COMPRESSOR FANS COMPRESSOR FANS
YCAS RATING
2
WIRE RANGE
7
(LUGS) RLA X-LRA FLA (ea) RLA X-LRA FLA (ea)
0130EC
460 273 400 (2) 3/0 - 250 107 579 4.0 107 579 4.0
575 217 250 # 6 AWG -150 86 463 3.1 86 463 3.1
0140EC
460 293 400 (2) 3/0 - 250 116 579 4.0 116 579 4.0
575 234 400 (2) 3/0 - 250 93 463 3.1 93 463 3.1
0150EC
460 307 400 (2) 3/0 - 250 128 856 4.0 115 579 4.0
575 246 400 (2) 3/0 - 250 103 715 3.1 92 463 3.1
0160EC
460 320 400 (2) 3/0 - 250 128 856 4.0 128 856 4.0
575 257 400 (2) 3/0 - 250 103 715 3.1 103 715 3.1
0170EC
460 335 400 (2) 3/0 - 250 140 856 4.0 128 856 4.0
575 268 400 (2) 3/0 - 250 112 715 3.1 103 715 3.1
0180EC
460 347 400 (2) 3/0 - 250 140 856 4.0 140 856 4.0
575 277 400 (2) 3/0 - 250 112 715 3.1 112 715 3.1
0200EC
460 375 630 (3) 2/0 - 400 149 856 4.0 149 856 4.0
575 299 400 (2) 3/0 - 250 119 715 3.1 119 715 3.1
0210EC
460 393 630 (3) 2/0 - 400 163 856 4.0 149 856 4.0
575 313 400 (2) 3/0 - 250 130 715 3.1 119 715 3.1
0230EC
460 407 630 (3) 2/0 - 400 163 856 4.0 163 856 4.0
575 324 400 (2) 3/0 - 250 130 715 3.1 130 715 3.1
Suitable for:
Across-the-Line-Start
One field-provided power supply circuit to the unit with
circuit protection. Field connections to factory-provided
Circuit Breaker in the Options Panel. Factory connections
to Terminal Blocks in each of the two Power Panels.
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION TO FACTORY CIRCUIT BREAKER
LD05900
See page 53 for Electrical Notes.