JOHNSON CONTROLS
301
SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
TABLE 33 - YORKTALK 2 COMMUNICATIONS DATA MAP
Item
1
2
3
4
5
6
7
8
9
10
Imperial
SI
Point List Description
1
2
3
4
5
6
7
8
9
10
1 REM_SETP
AV1 1026
03,06,16 Div 10 ADF 1 °F °C Remote Setpoint
S
2 DMD_LIMIT
AV2 1027
03,06,16 Div 10 ADF 2 % FLA % FLA Remote Current Limit Setpoint
S
3 SND_LIMIT
AV3 1028
03,06,16 Div 10 ADF 3 % % Remote Sound Limit
S
4 SPARE AV1 AV4 1029 03,06,16 Div 10 ADF 4 None None Spare
N
5 START_STOP BV1 1538 01,03,05,06,15 N/A
BD 1 0/1 0/1 Remote Start / Stop Command [0=Stop, 1=Run] S
6 SPARE_BV1 BV2 1539 01,03,05,06,15 N/A
BD 2 0/1 0/1 Spare N
7 SPARE_BV2 BV3 1540 01,03,05,06,15 N/A
BD 3 0/1 0/1 Spare N
8 SPARE_BV3 BV3 1541 01,03,05,06,15 N/A
BD 3 0/1 0/1 Spare N
9 LCHLT
AI1 514 03,04 x10 ADF 5 °F °C Leaving Chilled Liquid Temperature S
10 ECHLT
AI2 515 03,04 x10 ADF 6 °F °C Entering Chilled Liquid Temperature S
11 VSD_IA_TEMP AI3 516
03,04 x10 ADF 7 °F °C VSD Internal Ambient Temperature S
12 S1_SUCT_TEMP AI4 517
03,04 x10 ADF 8 °F °C Sys 1 Suction Temperature S
13 S2_SUCT_TEMP AI5 518
03,04 x10 ADF 9 °F °C Sys 2 Suction Temperature S
14
S3_SUCT_TEMP
AI6 519 03,04 x10 ADF 10 °F °C
Sys 3 Suction Temperature
S
15
S4_SUCT_TEMP
AI7 520 03,04 x10 ADF 11 °F °C
Sys 4 Suction Temperature
S
16 S1_DSCH_TEMP AI8 521
03,04 x10 ADF 12 °F °C Sys 1 Discharge Temperature S
17 S2_DSCH_TEMP AI9 522
03,04 x10 ADF 13 °F °C Sys 2 Discharge Temperature S
18 S3_DSCH_TEMP AI10 523
03,04 x10 ADF 14 °F °C Sys 3 Discharge Temperature S
19 S4_DSCH_TEMP AI11 524
03,04 x10 ADF 15 °F °C Sys 4 Discharge Temperature S
20 OAT
AI12 525 03,04 x10 ADF 16 °F °C Ambient Air Temperature S
21 S1_OIL_TEMP AI13 526
03,04 x10 ADF 17 °F °C Sys 1 Oil Temperature S
22 S2_OIL_TEMP AI14 527
03,04 x10 ADF 18 °F °C Sys 2 Oil Temperature S
23 S3_OIL_TEMP AI15 528
03,04 x10 ADF 19 °F °C Sys 3 Oil Temperature S
24 S4_OIL_TEMP AI16 529
03,04 x10 ADF 20 °F °C Sys 4 Oil Temperature S
25 S1_OIL_PRESS AI17 530
03,04 x10 ADF 21 PSI BAR Sys 1 Oil Pressure S
26 S2_OIL_PRESS AI18 531
03,04 x10 ADF 22 PSI BAR Sys 2 Oil Pressure S
27 S3_OIL_PRESS AI19 532
03,04 x10 ADF 23 PSI BAR Sys 3 Oil Pressure S
28 S4_OIL_PRESS AI20 533
03,04 x10 ADF 24 PSI BAR Sys 4 Oil Pressure S
29 S1_SUCT_PRES AI21 534
03,04 x10 ADF 25 PSI BAR Sys 1 Suction Pressure S
30 S2_SUCT_PRES AI22 535
03,04 x10 ADF 26 PSI BAR Sys 2 Suction Pressure S
31 S3_SUCT_PRES AI23 536
03,04 x10 ADF 27 PSI BAR Sys 3 Suction Pressure S
YCAV YCIV
Board: 031-03478Modbus, BACnet MS/TP, N2 Data Map
Comments
Y.ACS.14.03, Y.ACS.15.03, Y.ACS.16.03, Y.ACS.17.03,
Y.ACS.18.03, Y.ACS.19.03, Z.ACS.14.04, Z.ACS.15.03M,
Z.ACS.17.03, Z.ACS.19.04, Z.ACS.31.03
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Version York P/N
Item
Ref
Num
BACnet Name
BACnet
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
(See
Note 5)
New
031-03476-001, -002, -003, -
004, -005, -202, -101, -210, -
104, -AGR, -225
ANALOG WRITE POINTS
BINARY WRITE POINTS
ANALOG READ ONLY POINTS
YCAV
and YCIV Native
Property of Johnson Controls, Inc.
Subject to change without notice.
1 of 4
02/17/2017

Table of Contents

Questions and Answers: