EasyManuals Logo

York YCIV Series User Manual

York YCIV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
JOHNSON CONTROLS
56
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
WATER TEMPERATURE AND FLOWS
(ENGLISH UNITS)
MODEL NUM-
BER
YCIV
LEAVING WATER
TEMPERATURE (°F)
COOLER FLOW
(GPM)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0157(S/P/H) 40 60 140 675 0 125
0157(E/V) 40 60 160 750 0 125
0177(S/P/H) 40 60 160 750 0 125
0177(E/V) 40 60 160 750 0 125
0187(S/P/H) 40 60 160 750 0 125
0187(E/V) 40 60 160 750 0 125
0197(E/V) 40 60 180 750 0 125
0207(S/P/H) 40 60 180 800 0 125
0207(E/V) 40 60 180 750 0 125
0227(S/P/H) 40 60 180 800 0 125
0227(E/V) 40 60 180 750 0 125
0247(S/P/H) 40 60 180 800 0 125
0247(E/V) 40 60 180 800 0 125
0267(S/P/H) 40 60 180 800 0 125
0267(E/V) 40 60 250 1200 0 125
0287(S/P/H) 40 60 250 1200 0 125
0287(E/V) 40 60 250 1200 0 125
0307(S/P/H) 40 60 300 1200 0 125
0327(E/V) 40 60 300 1200 0 125
0357(S/P/H) 40 60 300 1200 0 125
0357(E/V) 40 60 300 1200 0 125
0397(S/P/H) 40 60 300 1200 0 125
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls o󰀩ce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls o󰀩ce for application guidelines.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCIV Series and is the answer not in the manual?

York YCIV Series Specifications

General IconGeneral
BrandYork
ModelYCIV Series
CategoryChiller
LanguageEnglish

Related product manuals