1.2.4 Parameters relating to probes
Parameters relating to probes
Display Description Level VS Unit Max. Min. Value
/01
NTC B1 probe (water inlet):
0=Always ON (function not available)
1= Present
F 1 (R/W) - 1 0 1
/02
NTC B2 probe (water outlet):
0=Always ON (function not available)
1= Present
F 2 (R/W) - 1 0 1
/03
NTC B3 probe:
1= Condensation probe
2= Outdoor probe
F 14 (R/W) - 1 0 (a)
/04
B4 probe:
0= Absent 1= ON/OFF
2= Outdoor NTC probe
3= Ratiometric 5 Vdc
F 15 (R/W) - 3 0 (b)
/09 Minimum input voltage F 18 (R/W) 0,01 Vdc /10 0 50
/10 Maximum input voltage F 19 (R/W) 0,01 Vdc 500 /09 450
/11 Minimum pressure F 1 (R/W) bar /12 0 0
/12 Maximum pressure F 2 (R/W) bar 99,9 /11 45
/13 B1 probe calibration F 3 (R/W) °C 12 -12 0
/14 B2 probe calibration F 4 (R/W) °C 12 -12 0
/15 B3 probe calibration F 5 (R/W) °C 12 -12 0
/16 B4 probe calibration F 6 (R/W) bar 12 -12 0
/21 Digital filter U 20 (R/W) - 15 1 4
/22 Inlet limitation U 21 (R/W) - 15 1 8
/23
Measuring unit:
0=C
1=1F
U 5 (R/W) - 1 0 0
b00 Probe viewed on display U 24 (R/W) - 7 0 0
b01 Value read by probe B1 D 70 (R) °C - - -
b02 Value read by probe B2 D 71 (R) °C - - -
b03 Value read by probe B3 D 72 (R) °C - - -
b04 Value read by probe B4 D 73 (R) °C/bar - - -
(a) YLCA/YLHA PLUS 5 to 15 /03=1; YLCA/YLHA PLUS 5 to 15 LAK /03=2; YLCA/YLHA PLUS 20 to 27 /03=2
(b) YLCA/YLHA PLUS 5 to 15 /04=2; YLCA/YLHA PLUS 5 to 15 LAK /04=3; YLCA/YLHA PLUS 20 to 27 /04=3
1.2.5 Parameters relating to the compressor
Parameters relating to the compressor
Display Description Level VS Unit Max. Min. Value
c01 Minimum operating time U 25 (R/W) Seconds 999 0 60
c02 Minimum stoppage time U 26 (R/W) Seconds 999 0 60
c03 Time between start-ups of one compressor U 27 (R/W) Seconds 999 0
300 (a)
240 (b)
c06 Start-up timing U 30 (R/W) Seconds 999 0 10
c07 Compressor start-up delay with regard to the pump U 31 (R/W) Seconds 150 0 20
c08 Pump stoppage delay with regard to the compressor U 32 (R/W) Minutes 150 0 1
c10 Operating hour counter for compressor D 90 (R) Hours 800 0 -
c14 Operating hour counter for compressor maintenance U 34 (R/W) Hours 100 0 0
c15 Operating hour counter for pump D 94 (R/W) Hours 800 0 -
c17 Minimum time between pump start-ups U 35 (R/W) Minutes 150 0 5
c18 Minimum operating time for pump U 36 (R/W) Minutes 15 0 1
(a) Units without Soft ‑ Start
(b) Units with Soft ‑ Start
User manual 1
Operating instructions µC2 1.2