3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 125/186
08 OPERATION
Alarm fault lamp
Flashing light: alarm
Permanent light: fault
Emergency-off reset pushbutton
Resets the emergency-off relay in the drive control system
Flashes when the auxiliary voltage is switched on, or when an
emergency-off switch is pressed
Emergency-off latching pushbutton
Prevents starting when pressed at standstill of the drive
Main circuit breaker opens and DC link discharges when pressed
during operation of the drive
8.5 Lamp-test function
The lights and illuminated pushbuttons on the control compartment can
be tested with the lamp-test function.
The lamp test is activated via the CDP control panel by setting control
parameter 16.7 to LAMP TEST. The lamp-test function resets itself after a
set time.
8.6 Status messages
The following section lists the status messages of the main operating
states that the drive passes through when:
Drive is put into operation (see 8.6.1 Start sequence of the drive
on page 127)
Drive is stopped (see 8.6.2 Stop sequence of the drive
on page 128)
Fault condition has occurred
The status messages are sent to the higher-level control system and are
displayed on the CDP control panel of the drive.
Note: For information on other status messages (eg, fault status
messages), see the status words in Appendix G Signal and
parameter table.