H108 Installation Guide
Name Description Recommended action
System_Warning. H2_OFF_RANGE The system will report this WARNING
when the hydrogen value is out of the
measurement range
This event indicates that
the hydrogen measurement
is outside its specified
maximum range
System_Warning. H2O_OFF_RANGE The system will report this WARNING
when the moisture value is out of the
measurement range
This event indicates that
the moisture measurement
is outside its specified
maximum range
System_Warning SYSTEM_LOW_SPACE The system will report this WARNING
when it is running out of disk space
Contact ABB Service
SYSTEM_CRITICAL . H2_SENSOR_FATAL_ERROR The system will report this ALARM
when the hydrogen probe is in a fatal
error condition
Power cycling may resolve
this issue. If the condition
persists, contact ABB
Service
SYSTEM_CRITICAL .H2_SENSOR_NOT_READY The system will report this ALARM
when the hydrogen probe does not
reach its ready state
Power cycling may resolve
this issue If the condition
persists, contact ABB
Service
SYSTEM_CRITICAL.NO_NEW_H2_MEASUREMENT The system will report this ALARM
when it is no longer able to
communicate with the hydrogen
probe
Contact ABB Service
SYSTEM_CRITICAL.NO_NEW_H2O_MEASUREMENT The system will report this ALARM
when it is no longer able to
communicate with the moisture
probe
Contact ABB Service
THERMAL_PUMP_DISABLED The system will report this Warning
when the thermal pump is not
enabled.