EasyManuals Logo
Home>ABB>Accessories>CoreSense

ABB CoreSense User Manual

ABB CoreSense
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
APPENDIX D
DNP3
The CoreSense DNP3 outstation implementation is compliant to level 1 and level 2. The CoreSense DNP3
device profile can be downloaded from www.abb.com. Out of the box, you can communicate with the
sensor using a default data link address = 4. DNP3 is available on the RS-485 serial interface or on the
Ethernet interfaces.
NOTICE
For best results, it is recommended to configure the DNP3 master with a time out of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The DNP3 cold restart function is not supported for cybersecurity reasons.
The default outstation ID is 4.
Default RS-485 configuration
Baud rate 9600
Data Bits 8
Stop bits 1
Parity None
Flow control None (only none is supported)
Default TCP configuration port
DNP3 20.000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CoreSense and is the answer not in the manual?

ABB CoreSense Specifications

General IconGeneral
BrandABB
ModelCoreSense
CategoryAccessories
LanguageEnglish

Related product manuals