APPENDIX D
DNP3
The CoreSense DNP3 outstation implementation is compliant to level 1 and level 2. The CoreSense DNP3
device profile can be downloaded from www.abb.com. Out of the box, you can communicate with the
sensor using a default data link address = 4. DNP3 is available on the RS-485 serial interface or on the
Ethernet interfaces.
NOTICE
For best results, it is recommended to configure the DNP3 master with a time out of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The DNP3 cold restart function is not supported for cybersecurity reasons.
The default outstation ID is 4.
Default RS-485 configuration
Baud rate 9600
Data Bits 8
Stop bits 1
Parity None
Flow control None (only none is supported)
Default TCP configuration port
DNP3 20.000