■ General parameters
These parameters are common to all safety functions in the FSO
module.
DescriptionExample
value
NameIndex
Sets the digital output that indicates the
completion of any stop function. Active
when the FSO module has completed
the STO, SSE or SS1 function.
None
1)
Stop completed
output
FSO-
GEN.11
Sets the nominal motor speed. Adjust
the default value to meet the ratings of
the motor in use.
1500.0 rpmMotor nominal
speed
FSO-
GEN.21
Sets the nominal motor frequency. Ad-
just the default value to meet the rat-
ings of the motor in use.
50.00 HzMotor nominal
frequency
FSO-
GEN.22
Sets the power-up acknowledgement
method of the FSO module.
AutomaticPower-up ac-
knowledge-
ment
FSO-
GEN.41
Automatic: You do not need to push a
reset button after switching on the FSO
module. The FSO module generates
the acknowledgement signal automat-
ically after the power-up.
Manual: The FSO module reads the
external acknowledgement signal
through the digital input defined by
parameter FSOGEN.42.
Make sure that the value is Automatic.
Sets the digital input for the acknow-
ledgement signal when parameter
STO.02 has value Manual.
None
1)
Acknowledge-
ment button in-
put
FSO-
GEN.42
Selects the digital input for the acknow-
ledgement signal when parameter
STO.02 has value Manual. In the safety
function described in this manual,
parameter STO.02 has value Automatic
and this parameter has value None (no
acknowledgement signal connected to
the input).
Parameter settings 55