L1, L2, L3
3
24VDC/0V
K
k1
DOC DO0 DO1 DO2
UMC100
On
Off-N
COM
230VAC
1
2
3
*)
Connecting Contactors
—
Actual ABB contactors - all currents for 230 V AC (Extract):
Contactor type Inrush current [A] Holding current [A] Inrush power [VA] Holding power [VA]
1)
The contactor B6S-30-10-2.8 (24 V DC) is recommended as interface contactor due to its internal spark suppression.
Spark suppression is necessary for all types except the AF types to maintain a reasonable service life.
—
Connection of contactors with electronic interface (AF types)
to the UMC100.3
*) Slide switch on the left side to position 'PLC' (up)
Connecting more than one expansion module
To connect several expansion modules to the UMC100.3 use the UMCIO-CAB cable to connect the first module with the UMC. And
use the IOIO-CAB cable to connect the first module with the second module and so on. The module order does not matter.