20
9 INSTALLER MENU
The INSTALLER menu is used to access many of the settings for operating and ad-
justing the unit; it may, however, contain parameters that should only be modied
by persons responsible for maintenance and/or assistance on the unit or system,
and for this reason it's protected by a password.
USER PASSWORD: 0000
9.1 ACCESS THE MENU VIA PASSWORD 0000
1
2
3
1. This key is used to quit the window and go back to the menu selection page
2. Indicates the current value of the password to be used for accessing the in-
staller menu
3. This key is used to conrm the access password entered
9.2 SUBMENU SELECTION PAGE
Enter the “LANGUAGE” submenu
Enter the “INFO” submenu
Enter the “CHILLER” submenu
Enter the “SYSTEM SIDE” submenu
Enter the “COUNTS submenu
Enter the “PASSWORD” submenu
Enter the “OPTIONS” submenu
Enter the “SYSTEM CONFIGURATIONS” submenu
9.3 SETTING THE LANGUAGE FOR THE USER INTERFACE
Used to set English as the system language
Used to set Italian as the system language
Used to set Russian as the system language
9.4 DISPLAY SOFTWARE VERSIONS OF THE BOARDS
Indicates the current software version installed on the pCO5+ control board
Indicates the current software version installed on the touch display board
Indicates the current software version installed on the turbocor compressors
board
Indicates the date and time of the test carried out at the factory of the unit, in
addition to the congured code of the unit
9.5 SELECTION OF THE ADJUSTMENT LOGIC IN COOLING
Sets the probe on which to base cooling adjustment. The potential choices are:
EVAP.INL. = Evaporator inlet;
EVAP.OUT. = Evaporator outlet;
COM.OUT. = Common evaporator outlet;
Sets the setting to be used for cold setpoint adjustment. The possible choices
are:
FIXED SETPOINT = The adjustment does not perform any dynamic correction on
the cold setpoint value;
SETPOINT COMPENS. = The cold setpoint is compensated based on the external
temperature by using the climatic curve (this adjustment is not available on the
water/water units);
Sets the dierential value to be applied to the cold setpoint
Select the type of adjustment to be used. The possible choices are:
PROPORTIONAL: Applies the proportional error;
PROP.+INTEGR: Applies proportional + integral error;
PID: NOT AVAILABLE;
Sets the integral time to be used in the adjustment algorithm

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC Turbocor C-Touch and is the answer not in the manual?

AERMEC Turbocor C-Touch Specifications

General IconGeneral
BrandAERMEC
ModelTurbocor C-Touch
CategoryControl Panel
LanguageEnglish

Related product manuals