Rockwell Automation Publication 1734-UM013N-EN-P - September 2017 17
POINT Guard I/O Overview Chapter 1
Safety Precautions
Observe these precautions for proper use of POINT Guard I/O modules.
Installing and Replacing Modules
When you clean a module, do not use the following:
• Thinner
• Benzene
• Acetone
ATTENTION: As serious injury can occur due to loss of required safety function,
follow these safety precautions.
• Never use test outputs as safety outputs. Test outputs are not safety outputs.
• Do not use Ethernet, DeviceNet, or ControlNet standard I/O data or explicit
message data as safety data.
• Do not use light-emitting diode (LED) status indicators on the I/O modules for
safety operations.
• Do not connect loads beyond the rated value to the safety outputs.
• Apply properly specified voltages to the module. Applying inappropriate
voltages can cause the module to fail to perform it’s specified function, which
could lead to loss of safety functions or damage to the module.
• Wire the POINT Guard I/O modules properly following the wiring requirements
and guidelines in Wire Modules
on page 61.
• Set unique network node addresses before connecting devices to the network.
• Perform testing to confirm that device wiring, configuration, and operation is
correct before starting system operation.
• Do not disassemble, repair, or modify the module. This can result in loss of
safety functions.
ATTENTION:
• Clear previous configuration data before connecting devices to the network or
connecting input or output power to the device.
• Configure the replacement device properly and confirm that it operates
correctly.
• After installation of the module, a safety administrator must confirm the
installation and conduct trial operation and maintenance.