9. Right-click the xxxx_Light tag name and
select New ‘xxxx_Light’.
xxxx_Light is an alias tag for the I/O
point tag name. This lets you assign a
simple name to a physical I/O point
address.
10. From the Type pull-down menu,
select Alias.
11. In the Alias For pull-down menu,
browse to a local 1769 digital output
module and select any bit.
In this example, Local:5:O.Data.0 is
used.
12. Click OK.
8. Name the Output Energize xxxx_Light (where xxxx is
the suffix of the catalog number of the 1769 Compact I/O
digital output module).
Important: Do not use spaces in the tag name. Use
underscores (_) instead.