EasyManuals Logo
Home>Allen-Bradley>I/O Systems>D Series

Allen-Bradley D Series User Manual

Allen-Bradley D Series
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
A
Appendix
A-1
Specifications
Module Location 1771 I/O chassis, leftmost slot
Chassis Distance
2500 ft @ 230.4K Baud
5000 ft @ 115.2K Baud
10000 ft @ 57.6K Baud
Interconnect Cable 1770-CD
Power Dissipation 5 Watts
Thermal Dissipation 17.06 BTU/hr
Backplane Current 1.0A @ 5V
Keying
Upper connector: between 54 and 56
Lower connector: between 16 and 18
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
0
o
to 60
o
C (32
o
to 140
o
F)
-40
o
to 85
o
C (-40
o
to 185
o
F)
5% to 95% (without condensation)
Field Wiring Arm Cat. No. 1771-WB
Field Wiring Arm Screw Torque 79 inchpounds