EasyManuals Logo
Home>Allen-Bradley>Controller>Logix5000

Allen-Bradley Logix5000 User Manual

Allen-Bradley Logix5000
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
76 Rockwell Automation Publication ENET-UM004B-EN-P - November 2015
Appendix A EtherNet/IP Communication Module Status Indicators
Status Indicators
The 5069-AEN2TR EtherNet/IP adapter has these status indicators.
Indicator State Description
OK Off There is no power applied to the device.
Steady green The device is operating in a normal condition.
Flashing red The device has a recoverable fault. The fault can be read from the device through the
USB or Ethernet ports.
A firmware update is being performed on the module.
Steady red The device has an unrecoverable fault. Minimum recovery is to power cycle.
SD Off There is no activity to the SD card.
Flashing green The controller is reading from, or writing to the SD card.
Flashing red The SD card does not have a valid file system.
NET Off The module is not configured, or does not have an IP address.
Flashing green The adapter has an IP address, but no active connections are established.
Steady green The adapter has an IP address and at least one established active connection.
Steady red Duplicate IP Address or invalid configuration.
LINK1 Off No activity. One of these conditions exists:
The module is not powered.
Verify that there is power.
Verify that the module RTB is properly seated in the adapter.
Verify that the RJ45 cables are properly seated in the adapter and connected devices.
• No link exists on the port.
Flashing green Activity exists on the port.
LINK2 Off No activity. One of these conditions exists:
The module is not powered.
Verify that there is power.
Verify that the module RTB is properly seated in the adapter.
Verify that the RJ45 cables are properly seated in the adapter and connected devices.
• No link exists on the port.
The port is administratively disabled.
The port is disabled due to rapid ring faults.
Flashing green Activity exists on the port.
Steady green Adapter is the supervisor of a Device Level Ring network.
MOD
Power
Off There is no Module Power applied to the device.
Steady green Module Power is present.
SA Power Off Status of SA Power is unknown.
Steady green SA Power is present.

Other manuals for Allen-Bradley Logix5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Logix5000 and is the answer not in the manual?

Allen-Bradley Logix5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLogix5000
CategoryController
LanguageEnglish

Related product manuals