Rockwell Automation Publication ENET-UM004B-EN-P - November 2015 79
Module Tags Appendix B
HMIPacketRate DINT The number of Class 3 packets and unconnected packets that are sent and received by the
device in the previous second.
All
IOPacketRate DINT The number of class 0 and class 1 packets transmitted or received by the adapter in the
previous second.
All positive values
EthernetErrors DINT The sum over all ports of the Ethernet Link object values: In Discards, In Errors, In
Unknown Protos, Out Discards, Out Errors, Alignment Errors, FCS Errors, Single Collisions,
Multiple Collisions, SQE Test Errors, Deferred Transmissions, Late Collisions, Excessive
Collisions, MAC Transmit Errors, Carrier Sense Errors, Frame Too Long, and MAC Receive
Errors.
All positive values
CPUUtilization INT The percentage of the capacity of the product's compute engine (whether that is a CPU, or
a core of a CPU, or a thread) most important to the performance of communication of
packets by the product. The value equals the percentage.
0…100
DLRNetworkState SINT The current value of the Network Status instance attribute of the DLR object for devices
with multiple Ethernet ports that support DLR.
0 - Normal
1 - Ring Fault
2 - Unexpected Loop Detected
3 - Partial Network Fault
4 - Rapid Fault/Restore Cycle
DLRSupervisorState SINT The current value of the Ring Supervisor Status instance attribute of the DLR object for
devices with multiple Ethernet ports that support DLR.
0 - Device is functioning as a backup
1 - Device is functioning as the active
ring supervisor
2 - Device is functioning as a normal ring
node
3 - Device is operating in a non-DLR
topology
4 - Device cannot support the current
ring parameters (Beacon Interval and
Beacon Timeout)
LocalClockOffset LINT The offset from the local clock to the system time. This value helps to detect steps in time.
This value updates when a PTP update is received.
All.
LocalClockOffsetTimestamp LINT The time when the Local Clock Offset was sampled. This value is initially zero, and the first
time stamp occurs when the module synchronizes with the master clock.
N/A
GrandMasterClockID SINT[8] The EUI-64 Identity of the CIP Sync Grandmaster clock the module is synced to. All
Table 13 - 5069-AEN2TR EtherNet/IP Adapter Module Tags
Tag Name Data Type Definition Valid Values

Other manuals for Allen-Bradley Logix5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Logix5000 and is the answer not in the manual?

Allen-Bradley Logix5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLogix5000
CategoryController
LanguageEnglish

Related product manuals