Publication 2098-IN003E-EN-P — April 2004
Specifications and Dimensions A-3
The table below lists general power specifications and requirements
for the Ultra3000 230V drives (2098-DSD-030x-xx, -075x-xx, and
-150x-xx).
1
Specification is for nominal voltage. The absolute limits are ±10%, or 88-265V
rms
.
2
The 2098-DSD-030x-xx, -075x-xx, and -150x-xx (230V) drives are limited to one contactor cycles per two minutes.
3
400 μs half wave sine.
4
Power initialization requires a short period of inrush current. Dual element time delay (slow blow) fuses are
recommended (refer to Fuse Specifications on page A-5).
Specification
Description
2098-DSD-030 2098-DSD-075 2098-DSD-150
AC Input and Auxiliary Input Voltage
1
100-240V
rms
Single-Phase
100-240V
rms
Three-Phase
AC Input Frequency 47 - 63 Hz
Main AC Input Current
2, 4
Nominal,
Maximum inrush, 230V ac input
28A
rms
50A (0-peak)
30A
rms
50A (0-peak)
46A
rms
68A (0-peak)
Auxiliary AC Input Current
Nominal, 115V ac input
Nominal, 230V ac input
Maximum inrush, 115V ac input
3
Maximum inrush, 230V ac input
3
1.0A
rms
0.5A
rms
47A (0-peak)
95A (0-peak)
1.0A
rms
0.5A
rms
47A (0-peak)
95A (0-peak)
1.0A
rms
0.5A
rms
47A (0-peak)
95A (0-peak)
Continuous Output Current 15A (0-peak) 35A (0-peak) 65A (0-peak)
Intermittent Output Current 30A (0-peak) 75A (0-peak) 150A (0-peak)
Bus Capacitance 2370 μF 4290 μF 7520 μF
Internal Shunt Resistance 35 Ohms 16.5 Ohms 9.1 Ohms
Shunt On 420V dc 420V dc 420V dc
Shunt Off 402V dc 402V dc 402V dc
Bus Overvoltage 452V dc 452V dc 452V dc
Internal Shunt
Continuous power
Peak power
50W
4.5 kW
50W
10 kW
180W
18 kW
External Shunt
Resistance
Continuous power
Peak power
30 Ohms (-0/+5%)
2.4 kW
6 kW
16.5 Ohms (-0/+5%)
4 kW
10 kW
9 Ohms (-0/+5%)
8 kW
19 kW
Energy Absorption Capability
115V ac input
230V ac input
211 Joules
117 Joules
381 Joules
211 Joules
669 Joules
370 Joules
Continuous Power Output
115V ac input
230V ac input
1.5 kW
3 kW
3.75 kW
7.5 kW
7.5 kW
15 kW