Compressor element outlet temperature
If the outlet temperature of the compressor element exceeds the shut-down level (factory setting 120
˚C / 248 ˚F, programmable) the compressor will be shut-down, alarm LED (5) will flash, automatic
operation LED (3) will go out and the following screen will appear:
Main screen with shut-down indication, element outlet temperature
The related pictograph
will appear flashing.
Press Scroll buttons (12) until the actual compressor element temperature appears.
Shut-down screen, element outlet temperature
The screen shows that the temperature at the outlet of the compressor element is 120 ˚C.
Switch off the voltage and remedy the trouble.
After remedying and when the shut-down condition has disappeared, switch on the voltage and restart
the compressor.
Motor overload
In the event of motor overload, the compressor will be shut-down, alarm LED (5) will flash,
automatic operation LED (3) will go out and the following screen will appear:
Instruction book
34 2920 7180 30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atlas Copco GA 30+ and is the answer not in the manual?

Atlas Copco GA 30+ Specifications

General IconGeneral
ModelGA 30+
CategoryAir Compressor
Power30 kW
Working Pressure7.5-13 bar
Cooling SystemAir-cooled
Noise Level69 dB(A)
FAD5.2 m³/min