IGS-NT Communication Guide
100
7.4.7 Gear teeth – writing
Request: 01 06 0B D0 00 7D 4A 36
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B D0 = Register address: Register number (43025) – 40001 = 3024 DEC => BD0 HEX
00 7D = Gear teeth > 125 DEC => 7D HEX
36 4A = Check field calculation (page 143) (write LSB MSB !)
Response: 01 06 0B D0 00 7D 4A 36
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B D0 = Register addres
00 7D = Set the setpoint gear teeth to > 7D HEC => 125 DEC = 125
36 A4 = Check field calculation (page 143)
7.4.8 Nominal Power – writing
Request: 01 06 0B C0 01 F4 8B C5
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B C0 = Register address: Register number (43009) – 40001 = 3008 DEC => BC0 HEX
01 F4 = Nominal power > 500 DEC => 1F4 HEC
C5 8B = Check field calculation (page 143) (write LSB MSB !)
Response: 01 06 0B C0 01 F4 8B C5
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B C0 = Register addres
01 F4 = Set the setpoint nominal power to > 1F4 HEC => 500 DEC = 500
C5 8B = Check field calculation (page 143)