EasyManuals Logo
Home>ComAp>Controller>InteliSys NTC BaseBox

ComAp InteliSys NTC BaseBox User Manual

ComAp InteliSys NTC BaseBox
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
IGS-NT Communication Guide
100
7.4.7 Gear teeth writing
Request: 01 06 0B D0 00 7D 4A 36
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B D0 = Register address: Register number (43025) 40001 = 3024 DEC => BD0 HEX
00 7D = Gear teeth > 125 DEC => 7D HEX
36 4A = Check field calculation (page 143) (write LSB MSB !)
Response: 01 06 0B D0 00 7D 4A 36
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B D0 = Register addres
00 7D = Set the setpoint gear teeth to > 7D HEC => 125 DEC = 125
36 A4 = Check field calculation (page 143)
7.4.8 Nominal Power writing
Request: 01 06 0B C0 01 F4 8B C5
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B C0 = Register address: Register number (43009) 40001 = 3008 DEC => BC0 HEX
01 F4 = Nominal power > 500 DEC => 1F4 HEC
C5 8B = Check field calculation (page 143) (write LSB MSB !)
Response: 01 06 0B C0 01 F4 8B C5
01 = Controller address
06 = Modbus function code (Write Single Registers (page 137))
0B C0 = Register addres
01 F4 = Set the setpoint nominal power to > 1F4 HEC => 500 DEC = 500
C5 8B = Check field calculation (page 143)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliSys NTC BaseBox and is the answer not in the manual?

ComAp InteliSys NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliSys NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals