IGS-NT Communication Guide
89
7.2.11 Answer message
Answer message start with # character followed by Gen-set name. Colon separates this header form return
codes of SMS commands. Answer message is generated during serving of received message and is sent in
case that 160 characters or end of received message are achieved. Answer message is sent to the originator
phone number. Tree dots at the end of message indicate separation and next following message.
Example:
#5:accesscode r8252,w8252 100,r8252
answer message
#Gen-setname: 144,ok,100
7.2.12 Examples of SMS commands
Here is following several examples of SMS messages addresses to controller IG/IS-NT with address 5, named
‘Gen-set name’. Access code in this controller is set to ‘accesscode’ and password is 1234’. In examples are
used setpoints and values 8276 Nomin.power, 10123 RPM, 8315 Controller Mode, 8235 binary inputs,
8296 Gen > f.
Example 1 reading value
SMS #5:accesscode r8276 read value 8276
Answer #Gen-set name:100
Example 2 adjusting setpoint
SMS
#5:accesscode p 1234,
r8276,w8276 110,r8276
read value 8276,
write 110,
read value 8276
Answer
#Gen-set name:ok,100,ok,110
Password was accepted, read value of 8276 is 100,
writing to 8276 was ok, new value of 8276 is 110
If wrong password sent: #Gen-set
name:p_er,100, w_pass, 100
Password was not accepted,
read value of 8276 is 100
writing to 8276 was not successful
read value of 8276 is still 100
Example 3 Gen-set control and delay time
SMS
#5:accesscode
r8276,c1,d30,r10123
read value 8276,
invoke gen-set command START,
delay 30 sec,
read value 10123
Answer #Gen-set name:110,ok,d_ok,1499
read value of 8276 is 110,
Gen-set command START was accepted,
confirm delay command,
read value of 10123 is 1499

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliSys NTC BaseBox and is the answer not in the manual?

ComAp InteliSys NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliSys NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals