IGS-NT Communication Guide
49
Using a web browser
Ethernet connection to controller makes possible using any web browser for basic monitoring and adjustment of
the controller. Simply put the IP address of the module into the address line in your web browser like
http://192.168.1.254 and then enter access code. In case of connection from web browser there is 5 minutes
timeout after closing the browser window. After that the client is automatically logged out.
Note: The IP addresses of the controllers must be accessible from the remote computer. If the remote
computer is connected into another LAN segment than the gen-sets are, there must be a gateway(s) that enable
direct traffic between the segments. If the remote computer is connected via Internet, then the internet gateway
of the LAN where gen-sets are connected must have public IP address, must allow incoming traffic and must
provide port forwarding from the external public IP to the different internal gen-set IPs according to the port
used.
Image 4.1 Internet gateway configuration example (port forwarding)
4.1.2 Equipment
Equipment needed
Controllerside -
Connection
Ethernet cable (page 85) to LAN, for point to point connection between PC and
controller use cross-wired cable
PC side ETHERNET connection
4.1.3 Available software for IG/IS-NT
Software GenConfig InteliMonitor WinScope
Applicable YES YES YES
4.2 Internet connection via AirGate
IMPORTANT: Every new device must be authorized after first time connected to the AirGate,
registered and obtained the AirGate ID. Go to the web page airgate.comap.cz to authorize your
device.
This connection type is used for connection to controllers/sites, that are connected to the Internet, however they
do not have public and static IP address. The controllers connect by themselves to the AirGate server and
cyclically ask whether there is a connection request from a client or not. On the other side the clients
(InteliMonitor, WebSupervisor) connect to the AirGate server instead of connecting directly to the controller. The

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliSys NTC BaseBox and is the answer not in the manual?

ComAp InteliSys NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliSys NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals