Page #103 background image
SiUS122226E Control Specification
Part 4 Functions and Control 97
4.2 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
Indoor fan operation cannot be made in multiple indoor units. (A forced fan command is made
during forced cooling operation.)
Determine Operation Mode
The system judges the operation mode command which is set by each room in accordance with the
procedure, and determines the operation mode of the system.
The following procedure is taken when the modes conflict with each other.
1. The system follows the mode which is set first. (First-push, first-set)
2. For the rooms where the different mode is set, standby mode is activated. (The operation lamp
blinks.)
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Forced heating operation
Wiring error check operation
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating operation
Discharging from capacitor
Stop
(R17361)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS-W Series and is the answer not in the manual?

Daikin 2MXS-W Series Specifications

General IconGeneral
BrandDaikin
Model2MXS-W Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals