SiUS122226E Functions for Wall Mounted / Floor Standing Type
Part 4 Functions and Control 59
2.4 Automatic Cooling/Heating Changeover
Outline When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C (64.4 ~ 86°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating Cooling switching point:
Tr Tt + 3.0°C (+ 5.4°F) (CTXS, FTXS, FTXR series)
Tr Tt + 2.5°C (+ 4.5°F) (FVXS series)
(2) Cooling Heating switching point:
Tr < Tt – 3.0°C (– 5.4°F) (CTXS, FTXS, FVXS series)
Tr < Tt – 2.5°C (– 4.5°F) (FTXR series)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating operation.
4. During initial operation
Tr Ts : Cooling operation
Tr < Ts : Heating operation
CTXS, FTXS Series
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22°C (71.6°F): Switch to heating
Heating → 27°C (80.6°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
FTXR Series
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 26.5°C (79.7°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
Target temperature + 3.0°C (+5.4°F)
Heating Operation
Target temperature – 3.0°C (–5.4°F)
Cooling Operation
(R21862)
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target temperature + 2.0°C (+3.6°F)
= Thermostat OFF
Target temperature + 3.0°C (+5.4°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
(R24030)
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target temperature + 1.5°C (+2.7°F)
= Thermostat OFF

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS-W Series and is the answer not in the manual?

Daikin 2MXS-W Series Specifications

General IconGeneral
BrandDaikin
Model2MXS-W Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals