EasyManuals Logo
Home>Daikin>Air Conditioner>2MXS-W Series

Daikin 2MXS-W Series User Manual

Daikin 2MXS-W Series
303 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #234 background imageLoading...
Page #234 background image
Check SiUS122226E
228 Part 6 Service Diagnosis
8.5 Four Way Valve Performance Check
Check No.13
R6000939
Start heating operation.
NO
YES
YES
Four way valve
coil resistance at
520 ~ 620 ?
NO
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
NO
YES
S80
voltage at 270 ~
360 VDC for 3 sec. after
compressor starts, and then at
about 14 ~ 18 VDC?
(Fig. 1)
Disconnect the four way valve coil
from the connector and check the
continuity.
(Fig. 1)
Voltage at S80
270 ~ 360 VDC
14 ~ 18 VDC
Time
Compressor
ON
3 sec.
< Caution on resetting the power supply >
 Be sure to wait for 30 sec. or more after turning off the power.
Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
S80
voltage at 0 VDC
with the outdoor unit
energized?

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS-W Series and is the answer not in the manual?

Daikin 2MXS-W Series Specifications

General IconGeneral
BrandDaikin
Model2MXS-W Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals