EasyManuals Logo
Home>Daikin>Air Conditioner>2MXS-W Series

Daikin 2MXS-W Series User Manual

Daikin 2MXS-W Series
303 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #218 background imageLoading...
Page #218 background image
Troubleshooting for Outdoor Unit SiUS122226E
212 Part 6 Service Diagnosis
7.16 Position Sensor Abnormality
Error Code H6
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS-W Series and is the answer not in the manual?

Daikin 2MXS-W Series Specifications

General IconGeneral
BrandDaikin
Model2MXS-W Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals