3-67
=The alarm is displayed when the control air temperature is out of "in-range" and defrosting
was performed three times while the control air temperature does not return to in-range.
H005
30min
Out range timer
=
SP+1
SP
4Hr 4Hr
Figure5
=Alarm is displayed when the temperature difference between the control sensor and record
sensor is 2˚C for 1 hour, or more.
H006
Supply air sensor (SS)
Data recorder for supply air (DSS)
DSSSS > 2˚C→H006