4-20
4.4.4 Refrigerant Recovery and Charge
(1) Schematic diagram
Service work
Service port
Remarks
Pressure Check
High pressure
w
q
Refrigerant recovery
and charge (R134a:
4.6Kgf)
[1] Refrigerant
Recovery
t
Recover refrigerant from port t
after operating
Automatic Pump-Down first.
r & t
Recover completely the refrigerant
left in the unit port r & t.
[2] Vacuum &
Dehydration
r & t
After recovering, vacauum from
port r & t.
The connection at port r is same
size at q for low pressure.
[3] Liquid charging
te
After vacuuming, charge liquid
refrigerant from t first and them
from e.
If not reached to the specified
amount 4.2 kgf, go to next below.
1. Operate Automatic Pump-Down
first and stop it using ON/OFF
switch after the compressor
stops during the Auto pump
down operation.
2. Charge liquid refrigerant from
port e.
Low pressure
e
LSV
et
r
q
w
Drier
ESV
EV
HSV
Receiver
Condenser
Check valve
DPR
ISV
DSV
BSV
SMV
service port
service port
Compressor
Evaporator
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LXE10E-A14 and is the answer not in the manual?

Daikin LXE10E-A14 Specifications

General IconGeneral
BrandDaikin
ModelLXE10E-A14
CategoryHeat Pump
LanguageEnglish

Related product manuals