4-18
4.4.3 Automatic pump down
An automatic pump down system is applied to the unit to prevent the unit from extra decrease of low
pressure due to pump down operation or burning of scroll compressor due to a close stop valve.
(1) Controller operation
Press the key twice to select the pump down mode, then, the LCD displays "P down".
Select "ON" by using key or key, and press the key to start the automatic pump down
operation.
M
Controller display
COMP. DEFROST IN RANGE DE-HUMID.
SUPPLY
RETURN
ALARM
R.H.
Pump down mode
Pump down completed
COMP. DEFROST IN RANGE DE-HUMID.
SUPPLY
RETURN
ALARM
R.H.
•When the pump down
operation is ended
abnormally, "E201"
(pump down malfunction)
will be displayed.
•When the pump down
operation is completed,
the unit stops state.
Press
key to start
pump down
Fig. 2
Fig. 1
Current indication mode
normal operation
G-set mode
(Energy saving setting)
Pump down operation
M M