Mains supply 3 x 525-600 V AC Normal overload 110% for 1 minute
Size: P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 15 18.5 22 30 37 45 55 75 90
IP20/Chassis B3 B3 B4 B4 B4 C3 C3 C4 C4
IP21/NEMA 1 B1 B1 B2 B2 C1 C1 C1 C2 C2
IP55/Type 12 B1 B1 B2 B2 C1 C1 C1 C2 C2
IP66/NEMA 4X B1 B1 B2 B2 C1 C1 C1 C2 C2
Output current
Continuous (3 x 525-550 V) [A] 23 28 36 43 54 65 87 105 137
Intermittent (3 x 525-550 V) [A] 25 31 40 47 59 72 96 116 151
Continuous (3 x 525-600 V) [A] 22 27 34 41 52 62 83 100 131
Intermittent (3 x 525-600 V) [A] 24 30 37 45 57 68 91 110 144
Continuous kVA (525V AC) [kVA] 21.9 26.7 34.3 41 51.4 61.9 82.9 100 130.5
Continuous kVA (575V AC) [kVA] 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5
Max. input current
Continuous (3 x 525-600 V) [A] 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3
Intermittent (3 x 525-600 V) [A] 23 28 36 43 54 65 87 105 137
Additional specifications
Estim. power loss at rated max. load [W]
4)
400 475 525 700 750 850 1100 1400 1500
IP20 max. cable cross-section (mains, motor,
brake
and load sharing)
[mm
2
]/[AWG]
IP55, IP66 max. cable cross-section (mains,
motor, brake and load
sharing) [mm
2
]/[AWG]
Max. cable cross-section with disconnect
Mains disconnect switch included:
Weight IP20 [kg] 12 12 23.5 23.5 23.5 35 35 50 50
Weight IP21/55 [kg] 23 23 27 27 27 45 45 65 65
Efficiency
4)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Table 10.8
5)
With brake and
load sharing 95/ 4/0
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AI02 - VLT
®
is a registered Danfoss trademark
73