8 Warnings and Alarms
8.1 System Monitoring
The frequency converter monitors the condition of its
input
power, output, and
motor factors as well as other
system performance indicators. A warning or alarm may
not necessarily indicate a problem internal to the
frequency converter itself. In many cases, it indicates failure
conditions from input voltage, motor load or temperature,
external signals, or other areas monitored by the frequency
converter’s internal logic. Be sure to investigate those areas
exterior to the frequency converter as indicated in the
alarm or warning.
8.2 Warning and Alarm Types
Warnings
A warning is issued
when an alarm condition is impending
or when an abnormal operating condition is present and
may result in the frequency converter issuing an alarm. A
warning clears by itself when the abnormal condition is
removed.
Alarms
Trip
An alarm is issued when the frequency converter is
tripped, that is, the frequency converter suspends
operation to prevent frequency converter or system
damage. The motor will coast to a stop. The frequency
converter logic will continue to operate and monitor the
frequency converter status. After the fault condition is
remedied, the frequency converter can be reset. It will
then be ready to start operation again.
A trip can be reset in any of 4 ways
Press [Reset] on the LCP
Digital reset input command
Serial communication reset input command
Auto reset
An alarm that causes the frequency converter to trip-lock
requires that input power is cycled. The motor will coast to
a stop. The frequency converter logic will continue to
operate and monitor the frequency converter status.
Remove input power to the frequency converter and
correct the cause of the fault, then restore power. This
action puts the frequency converter into a trip condition as
described above and may be reset in any of those 4 ways.
8.3 Warning and Alarm Displays
130BP085.11
Status
0.0H
z
0.0Hz
1:0 - Off
!Live zero error [W2]
Off Remote Stop
!1(1)
Illustration 8.1 Warning Display
An alarm or trip-lock alarm will flash on display along with
the alarm number.
130BP086.11
Status
0.0H
z
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
Illustration 8.2 Alarm Display
In addition to the text and alarm code on the frequency
converter
LCP, there are
three status indicator lights.
Auto
on
Reset
Hand
on
Off
Back
Cancel
Info
OK
On
Alarm
Warn.
130BB467.10
Illustration 8.3 Status Indicator Lights
Warnings and Alarms
VLT
®
HVAC Drive Operating Instructions
54 MG11AI02 - VLT
®
is a registered Danfoss trademark
88
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Other manuals for Danfoss 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 102 and is the answer not in the manual?

Danfoss 102 Specifications

General IconGeneral
BrandDanfoss
Model102
CategoryMedia Converter
LanguageEnglish

Related product manuals