Enclosure size Power [kW] Recommended fuse size Recommended max. fuse
Recommended circuit
breaker
Danfoss
Max
trip
level
[A]
A3
1.1 gG-6 gG-25 CTI25M
10-16 16
1.5 gG-6 gG-25 CTI25M 10-16 16
2.2 gG-6 gG-25 CTI25M 10-16 16
3 gG-10 gG-25 CTI25M 10-16 16
4 gG-10 gG-25 CTI25M 10-16 16
5.5 gG-16 gG-25 CTI25M 10-16 16
7.5 gG-16 gG-25 CTI25M 10-16 16
B2
11 gG-25 gG-63
15 gG-25 gG-63
18 gG-32
22 gG-32
C2
30 gG-40
37 gG-63 gG-80
45 gG-63 gG-100
55 gG-80 gG-125
75 gG-100 gG-160
C3
37 gG-100 gG-125
45 gG-125 gG-160
D
37 gG-125 gG-125
45 gG-160 gG-160
55-75 gG-200 gG-200
90 aR-250 aR-250
110 aR-315 aR-315
132-160 aR-350 aR-350
200 aR-400 aR-400
250 aR-500 aR-500
315 aR-550 aR-550
E
355-400 aR-700 aR-700
500-560 aR-900 aR-900
F
630-900 aR-1600 aR-1600
1000 aR-2000 aR-2000
1200 aR-2500 aR-2500
Table 10.13 525-690 V, Frame Sizes A, C, D, E and F (non UL fuses)
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AI02 - VLT
®