Humidity sensor -
Min signal
Humidity sensor -
Max signal
Humidity ctrl. at de-
frost
Select how to control humidity during defrost:No: Hu-
midity control is stopped during defrostYes: Normal
humidity control is running during defrost
Maximum limit for thermostat air temperature in or-
der for humidity control to run (frost limit)
Minimum limit for thermostat air temperature in or-
der for humidity control to run (frost limit)
Injection control
Table 32: Injection control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
13=Not_used, 14=Defrost, 15=Fan delay, 17=Door
open, 18=Melt period, 19=Modulating temp. control,
20=Emergency control, 23=Adaptive superheat con-
trol, 24=Start injection, 25=Manual control, 26=No re-
frigerant selected, 16=Forced closing, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Actual status of output function
Actual status of output function
Temperature converted from pressure
Readout of actual superheat at the outlet of the evap-
orator
Readout of the actual superheat reference
Min. value for the superheat reference
Max. value for the superheat reference
MOP temperature. The valve opening degree is re-
duced until the evaporating temperature reaches the
set MOP limit. If no MOP function is required, select
the highest value that corresponds to OFF
Period time for the pulse width modulation
Min. superheat liq-
uid ctrl A
Min. value for the superheat reference during adap-
tive liquid control
Max. superheat liq-
uid ctrl. A
Max. value for the superheat reference during adap-
tive liquid control
Closing delay for liquid line solenoid valve
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 53
AK-CC55 Single Coil and Single Coil UI