Controller functionality
Functions
Day/night thermostat with ON/OFF or modulating principle
Product sensor S6 with separate alarm limits
Switch between thermostat settings via digital input
Adaptive control of superheat
Adaptive defrosting based on diagnostics
Start of defrost via schedule, digital input, network or setting display
Natural, electric or hot gas defrost
Stop of defrost on time and/or temperature
Coordination of defrosting among several controllers in a line-up
Pulsing or ECO control of fans when thermostat is satised
Appliance cleaning function for documentation of HACCP procedure
Rail heat control via day/night load or dewpoint
Humidity control in cold storage rooms
Door function
Control of two compressors
Control of night blinds
Light control
Heat thermostat
High accuracy inputs will guarantee a better measuring accuracy than stated in the standard EN ISO 23953-2
without subsequent calibration (Pt 1000 ohm sensor)
Integrated MODBUS communication with the option of mounting a LonWorks communication card
Liquid injection by use of AKV
Liquid injection in the evaporator is controlled by an electronic injection valve of the type AKV. The valve operates
as both expansion valve and solenoid valve. The controller opens and closes the valve based on sensor readings.
The function contains an adaptive algorithm which independently adjusts the valve’s opening so that the
evaporator constantly supplies optimum amount of refrigerant.
Liquid injection by use of stepper valve
Instead of AKV, an external stepper driver can be connected to AO1 (0 – 10 V) to drive a stepper valve. DO1 (AKV
output) is then congured to close a liquid line solenoid valve (LLSV) when a valve output is 0%. The LLSV is also
closed at power failure.
Superheat is measured via:
Pressure sensor Pe and temperature sensor S2. By using a pressure sensor, and temperature sensor a correct
measurement of superheat is achieved under all conditions which ensures a very robust and precise control. The
signal from one pressure transmitter can be shared by max. 10 controllers, but only if there is no signicant pressure
dierence between the evaporators in question.
There are two parallel settings for superheat:
Dry expansion, which does not allow liquid ow on the outlet of the evaporator.
Adaptive liquid control in transcritical CO
2
systems, which allows liquid ow. This type of control requires that the
controller receives an on/o signal from (for example) a suction accumulator in the suction line. A level switch in
the tank will register when the liquid level exceeds the max. level. When this happens, the controller will switch to
dry expansion, and then back to liquid control when the liquid level has dropped. The function is dened in
setting o02, o37 or o84.
The function can also be activated via data communication from a system unit. If the adaptive liquid control signal is
lost, the controller will automatically switch back to dry expansion.
© Danfoss | Climate Solutions | 2021.02 BC364229688105en-000101 | 9
AK-CC55 Single Coil and Single Coil UI

Table of Contents

Other manuals for Danfoss AK-CC55

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 and is the answer not in the manual?

Danfoss AK-CC55 Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55
CategoryController
LanguageEnglish

Related product manuals