4 Troubleshooting
4.1 Troubleshooting
A warning or an alarm is signalled by the relevant LED on
the front of the frequency converter and indicated by a
code on the display.
A warning remains active until its cause is no longer
present. Under certain circumstances, operation of the
motor may still be continued.
In the event of an alarm, the frequency converter trips. To
restart operation, reset the alarms once their causes have
been rectied.
This may be done in 4 ways:
By resetting the [RESET] on the LCP.
Via a digital input with the Reset function.
Via serial communication/optional eldbus.
By resetting automatically using the auto reset-
function, which is a default setting, see
parameter 14-20 Reset Mode.
NOTICE
After a manual reset pressing [RESET] on the LCP, press
[Auto On] or [Hand On] to restart the motor.
If an alarm cannot be reset, the reason may be that its
cause has not been rectied, or the alarm is trip-locked
(see also Table 4.1).
CAUTION
Alarms that are trip-locked oer additional protection, as
the mains supply must be switched o before the alarm
can be reset. After being switched back on, the
frequency converter is no longer blocked and may be
reset as described above once the alarm cause has been
rectied.
Alarms that are not trip-locked can also be reset using
the automatic reset function in parameter 14-20 Reset
Mode (Warning: Automatic wake-up is possible!)
If a warning and alarm is marked against a code in
Table 4.1, this means that either a warning occurs before
an alarm, or it can be specied whether it is a warning
or an alarm that is to be displayed for a given fault.
This is possible, for instance, in parameter 1-90 Motor
Thermal Protection. After an alarm or trip, the motor
carries on coasting, and the alarm and warning ash on
the frequency converter. Once the problem has been
rectied, only the alarm continues ashing.
NOTICE
No missing motorphase detection (number 30-32) and
no stall detection are active when parameter 1-10 Motor
Construction is set to [1] PM non-salient SPM.
No. Description Warning Alarm/trip Alarm/trip lock Parameter reference
1 10 V low X
2 Live zero error (X) (X)
Parameter 6-01 Live Zero
Timeout Function
3 No motor (X)
Parameter 1-80 Function
at Stop
4 Mains phase loss (X) (X) (X)
Parameter 14-12 Functio
n at Mains Imbalance
5 DC link voltage high X
6 DC link voltage low X
7 DC over voltage X X
8 DC under voltage X X
9 Inverter overloaded X X
10 Motor ETR over temperature (X) (X)
Parameter 1-90 Motor
Thermal Protection
11 Motor thermistor over temperature (X) (X)
Parameter 1-90 Motor
Thermal Protection
12 Torque limit X X
13 Over Current X X X
14 Ground fault X X X
Troubleshooting Programming Guide
MG11CE02 Danfoss A/S © 03/2015 All rights reserved. 209
4 4

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals