3.4 Parameters: 2-** Main Menu - Brakes
3.4.1 2-0* DC-Brakes
Parameter group for conguring the DC brake and DC hold
functions.
2-00 DC Hold/Preheat Current
Range: Function:
50
%*
[ 0 -
160
%]
NOTICE
Parameter 2-00 DC Hold/Preheat Current has
no eect when parameter 1-10 Motor
Construction=[1] PM, non-salient SPM.
NOTICE
The maximum value depends on the rated
motor current.
Avoid 100% current for too long. It may
damage the motor.
Enter a value for holding current as a percentage
of the rated motor current I
M,N
set in
parameter 1-24 Motor Current. 100% DC hold
current corresponds to I
M,N
.
This parameter holds the motor (holding torque)
or preheats the motor.
This parameter is active if [1] DC hold/Motor
Preheat is selected in parameter 1-80 Function at
Stop.
2-01 DC Brake Current
Range: Function:
50
%*
[ 0 -
1000
%]
NOTICE
The maximum value depends on the rated
motor current. Avoid 100 % current for too
long. It may damage the motor.
Enter a value for current as a percentage of the
rated motor current I
M,N
, see parameter 1-24 Motor
Current. 100% DC braking current corresponds to
I
M,N
.
DC brake current is applied on a stop command,
when the speed is lower than the limit set in
Parameter 2-03 DC Brake Cut In Speed
[RPM].
Parameter 2-04 DC Brake Cut In Speed
[Hz]; when the DC brake inverse function
is active; or via the serial communication
port.
The braking current is active during the time
period set in parameter 2-02 DC Braking Time.
2-02 DC Braking Time
Range: Function:
10 s* [0 - 60 s]
Set the duration of the DC brake current set in
parameter 2-01 DC Brake Current, once
activated.
2-03 DC Brake Cut In Speed [RPM]
Range: Function:
Size
related*
[ 0 - 0
RPM]
NOTICE
Parameter 2-03 DC Brake Cut In Speed
[RPM] has no eect when
parameter 1-10 Motor
Construction=[1] PM, non-salient
SPM.
Set the DC brake cut-in speed for
activation of the DC braking current set in
parameter 2-01 DC Brake Current, upon a
stop command.
When parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM, this value is
limited to 0 rpm (OFF)
2-04 DC Brake Cut In Speed [Hz]
Range: Function:
Size
related*
[ 0 -
0.0 Hz]
NOTICE
Parameter 2-04 DC Brake Cut In Speed
[Hz] has no eect when
parameter 1-10 Motor
Construction=[1] PM, non-salient
SPM.
This parameter is for setting the DC brake
cut-in speed at which the DC braking
current (parameter 2-01 DC Brake Current) is
to be active in connection with a stop
command.
2-06 Parking Current
Range: Function:
50
%*
[ 0 -
1000 %]
NOTICE
Parameter 2-06 Parking Current and
parameter 2-07 Parking Time: Only active
if PM motor construction is selected in
parameter 1-10 Motor Construction.
Set current as percentage of rated motor
current, parameter 1-24 Motor Current. Active in
connection with parameter 1-73 Flying Start. The
parking current is active during the time period
set in parameter 2-07 Parking Time.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
54 Danfoss A/S © 03/2015 All rights reserved. MG11CE02
33

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals