3.5 Parameters: 3-** Main Menu -
Reference/Ramps
3.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits, and
ranges.
See also parameter group 20-0* FC Closed Loop for
information on settings in closed loop.
3-02 Minimum Reference
Range: Function:
Size
related*
[ -999999.999 -
par. 3-03
ReferenceFeed-
backUnit]
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references. The minimum reference
value and unit match the congu-
ration made in
parameter 1-00
Conguration Mode
and 20-12 Reference/Feedback Unit.
NOTICE
This parameter is used in
open loop only.
3-03 Maximum Reference
Range: Function:
Size
related*
[ par. 3-02 -
999999.999
ReferenceFeed-
backUnit]
Enter the maximum reference. The
maximum reference is the highest
value obtainable by summing all
references.
The maximum reference unit
matches:
•
The conguration selected
in 1-00 Conguration
Mode: for [1] Speed closed
loop, RPM; for [2] Torque,
Nm.
•
The unit selected in
3-00 Reference Range.
3-04 Reference Function
Option: Function:
[0] Sum Sums both external and preset reference
sources.
[1] External/
Preset
Use either the preset or the external reference
source.
Shift between external and preset via a
command on a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0/1/2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1* Digital Inputs.
3-10 Preset Reference
Array [8]
Range: Function:
0
%*
[-100 -
100 %]
Enter up to 8 dierent preset references (0-7) in
this parameter, using array programming. The
preset reference is stated as a percentage of the
value Ref
MAX
(3-03 Maximum Reference, for closed
loop see parameter 20-14 Maximum Reference/
Feedb.). When using preset references, select
Preset ref. bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in parameter group
5-1* Digital Inputs.
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12
(+24V)
11001100
32
11110000
33
130BA149.10
Illustration 3.16 Preset Reference Scheme
Parameter Descriptions
VLT
®
HVAC Drive FC 102
58 Danfoss A/S © 03/2015 All rights reserved. MG11CE02