3.5 Parameters: 3-** Main Menu -
Reference/Ramps
3.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits, and
ranges.
See also parameter group 20-0* FC Closed Loop for
information on settings in closed loop.
3-02 Minimum Reference
Range: Function:
Size
related*
[ -999999.999 -
par. 3-03
ReferenceFeed-
backUnit]
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references. The minimum reference
value and unit match the congu-
ration made in
parameter 1-00
Conguration Mode
and 20-12 Reference/Feedback Unit.
NOTICE
This parameter is used in
open loop only.
3-03 Maximum Reference
Range: Function:
Size
related*
[ par. 3-02 -
999999.999
ReferenceFeed-
backUnit]
Enter the maximum reference. The
maximum reference is the highest
value obtainable by summing all
references.
The maximum reference unit
matches:
The conguration selected
in 1-00 Conguration
Mode: for [1] Speed closed
loop, RPM; for [2] Torque,
Nm.
The unit selected in
3-00 Reference Range.
3-04 Reference Function
Option: Function:
[0] Sum Sums both external and preset reference
sources.
[1] External/
Preset
Use either the preset or the external reference
source.
Shift between external and preset via a
command on a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0/1/2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1* Digital Inputs.
3-10 Preset Reference
Array [8]
Range: Function:
0
%*
[-100 -
100 %]
Enter up to 8 dierent preset references (0-7) in
this parameter, using array programming. The
preset reference is stated as a percentage of the
value Ref
MAX
(3-03 Maximum Reference, for closed
loop see parameter 20-14 Maximum Reference/
Feedb.). When using preset references, select
Preset ref. bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in parameter group
5-1* Digital Inputs.
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12
(+24V)
11001100
32
11110000
33
130BA149.10
Illustration 3.16 Preset Reference Scheme
Parameter Descriptions
VLT
®
HVAC Drive FC 102
58 Danfoss A/S © 03/2015 All rights reserved. MG11CE02
33

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals