EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 300

Danfoss VLT AutomationDrive FC 300 User Manual

Danfoss VLT AutomationDrive FC 300
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
1-04 Overload Mode
Option: Function:
[0] * High torque Allows up to 160% over torque.
[1] Normal torque For oversized motor - allows up to 110%
over torque.
NOTE
This parameter cannot be adjusted while the motor is
running.
1-90 Motor Thermal Protection
Option: Function:
Thermal motor protection can be
implemented using a range of techniques:
Via a PTC sensor in the motor
windings connected to one of the
analog or digital inputs
(1-93 Thermistor Source). See
6.1.3.1 PTC Thermistor Connection.
Via a KTY sensor in the motor
winding connected to an analog
input (1-96 KTY Thermistor Resource).
See 6.1.3.2 KTY Sensor Connection.
Via calculation (ETR = Electronic
Thermal Relay) of the thermal load,
based on the actual load and time.
The calculated thermal load is
compared with the rated motor
current I
M,N
and the rated motor
frequency f
M,N
. See 6.1.3.3 ETR and .
Via a mechanical thermal switch
(Klixon type). See 6.1.3.4 ATEX ETR.
For the North American market: The ETR
functions provide class 20 motor overload
protection in accordance with NEC.
[0]
* No
protection
Continuously overloaded motor, when no
warning or trip of the frequency converter is
required.
[1] Thermistor
warning
Activates a warning when the connected
thermistor or KTY-sensor in the motor reacts
in the event of motor over-temperature.
[2] Thermistor
trip
Stops (trips) frequency converter when
connected thermistor or KTY sensor in the
motor reacts in the event of motor over-
temperature.
The thermistor cut-out value must be > 3
k.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3] ETR warning
1
Calculates the load when set-up 1 is active
and activates a warning on the display when
1-90 Motor Thermal Protection
Option: Function:
the motor is overloaded. Programme a
warning signal via one of the digital outputs.
[4] ETR trip 1 Calculates the load when set-up 1 is active
and stops (trips) frequency converter when
the motor is overloaded. Programme a
warning signal via one of the digital outputs.
The signal appears in the event of a warning
and if the frequency converter trips (thermal
warning).
[5] ETR warning
2
[6] ETR trip 2
[7] ETR warning
3
[8] ETR trip 3
[9] ETR warning
4
[10] ETR trip 4
NOTE
If [20] is selected, follow strictly the instructions described
in the dedicated chapter of the VLT AutomationDrive
design guide and the instructions given by the motor
manufacturer.
NOTE
If [20] is selected, 4-18 Current Limit must be set to 150%.
6.1.3.1 PTC Thermistor Connection
1330
550
250
-20°C
175HA183.10
4000
3000
R
(Ω)
nominel
nominel -5°C
nominel +5°C
[°C]
Illustration 6.2 PTC profile
Using a digital input and 10 V as power supply:
How to Programme the Low Ha... VLT Automation Low Harmonic Drive Operating Instructions
70 MG34O202 - VLT
®
is a registered Danfoss trademark
6
6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals